Filtered by vendor Schneider-electric
Subscriptions
Total
786 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2017-7574 | 1 Schneider-electric | 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine | 2025-04-20 | 9.8 Critical |
| Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. | ||||
| CVE-2017-6032 | 1 Schneider-electric | 2 Modbus, Modbus Firmware | 2025-04-20 | N/A |
| A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks. | ||||
| CVE-2016-5818 | 1 Schneider-electric | 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device. | ||||
| CVE-2017-7971 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate. | ||||
| CVE-2017-9631 | 1 Schneider-electric | 1 Wonderware Archestra Logger | 2025-04-20 | 7.5 High |
| A Null Pointer Dereference issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The null pointer dereference vulnerability could allow an attacker to crash the logger process, causing a denial of service for logging and log-viewing (applications that use the Wonderware ArchestrA Logger continue to run when the Wonderware ArchestrA Logger service is unavailable). | ||||
| CVE-2017-6034 | 1 Schneider-electric | 2 Modbus, Modbus Firmware | 2025-04-20 | N/A |
| An Authentication Bypass by Capture-Replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download. | ||||
| CVE-2017-7967 | 1 Schneider-electric | 1 Vampset | 2025-04-20 | N/A |
| All versions of VAMPSET software produced by Schneider Electric, prior to V2.2.189, are susceptible to a memory corruption vulnerability when a corrupted vf2 file is used. This vulnerability causes the software to halt or not start when trying to open the corrupted file. This vulnerability occurs when fill settings are intentionally malformed and is opened in a standalone state, without connection to a protection relay. This attack is not considered to be remotely exploitable. This vulnerability has no effect on the operation of the protection relay to which VAMPSET is connected. As Windows operating system remains operational and VAMPSET responds, it is able to be shut down through its normal closing protocol. | ||||
| CVE-2017-7575 | 1 Schneider-electric | 2 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware | 2025-04-20 | N/A |
| Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded. | ||||
| CVE-2016-8352 | 1 Schneider-electric | 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code. | ||||
| CVE-2016-8354 | 1 Schneider-electric | 1 Unity Pro | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions. | ||||
| CVE-2016-8367 | 1 Schneider-electric | 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more | 2025-04-20 | 5.3 Medium |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. | ||||
| CVE-2017-7972 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes. | ||||
| CVE-2017-14024 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
| A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges. | ||||
| CVE-2017-7974 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
| A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. | ||||
| CVE-2017-6017 | 1 Schneider-electric | 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more | 2025-04-20 | N/A |
| A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. | ||||
| CVE-2016-5809 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. | ||||
| CVE-2016-5815 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. | ||||
| CVE-2017-7968 | 1 Schneider-electric | 1 Wonderware Indusoft Web Studio | 2025-04-20 | N/A |
| An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges. | ||||
| CVE-2020-25178 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 7.5 High |
| ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. | ||||
| CVE-2020-25182 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2025-04-16 | 6.7 Medium |
| Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. | ||||