Filtered by vendor Schneider-electric
Subscriptions
Total
789 CVE
| CVE | Vendors | Products | Updated | CVSS v3.1 |
|---|---|---|---|---|
| CVE-2017-7968 | 1 Schneider-electric | 1 Wonderware Indusoft Web Studio | 2025-04-20 | N/A |
| An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges. | ||||
| CVE-2017-7970 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to specify Arbitrary Server Target Nodes in connection requests to the Secure Gateway and Server components. | ||||
| CVE-2017-7971 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate. | ||||
| CVE-2017-7973 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
| A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database. | ||||
| CVE-2017-7974 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
| A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. | ||||
| CVE-2017-7575 | 1 Schneider-electric | 2 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware | 2025-04-20 | N/A |
| Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded, modified, and uploaded. | ||||
| CVE-2017-7574 | 1 Schneider-electric | 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine | 2025-04-20 | 9.8 Critical |
| Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. | ||||
| CVE-2017-6033 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2025-04-20 | N/A |
| A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path. | ||||
| CVE-2017-5155 | 1 Schneider-electric | 1 Wonderware Historian | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well. | ||||
| CVE-2016-8352 | 1 Schneider-electric | 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code. | ||||
| CVE-2016-8354 | 1 Schneider-electric | 1 Unity Pro | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions. | ||||
| CVE-2016-8367 | 1 Schneider-electric | 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more | 2025-04-20 | 5.3 Medium |
| An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack. | ||||
| CVE-2016-5818 | 1 Schneider-electric | 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware | 2025-04-20 | N/A |
| An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device. | ||||
| CVE-2017-9960 | 1 Schneider-electric | 1 U.motion Builder | 2025-04-20 | N/A |
| An information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system response to error provides more information than should be available to an unauthenticated user. | ||||
| CVE-2017-7907 | 1 Schneider-electric | 1 Wonderware Historian Client | 2025-04-20 | N/A |
| An Improper XML Parser Configuration issue was discovered in Schneider Electric Wonderware Historian Client 2014 R2 SP1 and prior. An improperly restricted XML parser (with improper restriction of XML external entity reference, or XXE) may allow an attacker to enter malicious input through the application which could cause a denial of service or disclose file contents from a server or connected network. | ||||
| CVE-2017-7967 | 1 Schneider-electric | 1 Vampset | 2025-04-20 | N/A |
| All versions of VAMPSET software produced by Schneider Electric, prior to V2.2.189, are susceptible to a memory corruption vulnerability when a corrupted vf2 file is used. This vulnerability causes the software to halt or not start when trying to open the corrupted file. This vulnerability occurs when fill settings are intentionally malformed and is opened in a standalone state, without connection to a protection relay. This attack is not considered to be remotely exploitable. This vulnerability has no effect on the operation of the protection relay to which VAMPSET is connected. As Windows operating system remains operational and VAMPSET responds, it is able to be shut down through its normal closing protocol. | ||||
| CVE-2017-7969 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack. | ||||
| CVE-2017-7972 | 1 Schneider-electric | 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert | 2025-04-20 | N/A |
| A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes. | ||||
| CVE-2016-5809 | 1 Schneider-electric | 6 Ion5000, Ion7300, Ion7500 and 3 more | 2025-04-20 | N/A |
| An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. | ||||
| CVE-2017-13997 | 1 Schneider-electric | 2 Wonderware Indusoft Web Studio, Wonderware Intouch | 2025-04-20 | N/A |
| A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server. | ||||